Appendix B 218IF Messages

B.1.2 MEMOBUS Binary Mode

B-10

„

Input Register Read (Expanded)

MFC: 20H

SFC: 0AH

Length: 08H

SPARE

CPU No.

Set the command length.

Command

The SFC number is 0AH when the input register contents are

read.
Set 4 bits each for the destination CPU number and the source

CPU number.

Set the leading address of the input registers to be read.

Set the number of input registers to be read.

(L)

(H)

Reference No.

No. of registers (n)

(L)

(H)

(L)

(H)

7

0

Always 20H.

MFC: 20H

SFC: 0AH

Length: 06H+

SPARE

CPU No.

Data 1

Data n

(L)

(H)

(L)

(H)

(L)

(H)

(L)

(H)

Set the command length.

Response

Always 20H.
The same SFC number as that specified in the command is

returned.
Set 4 bits each for the destination CPU number and the source

CPU number.

The read input register contents are returned.

The number of read input registers is returned.

7

0

No.of registers×2

No. of registers (n)