D.1 In-panel Wiring

D-3

D

D.1 In-panel Wiring

D.1.1 Connection Methods

„

215IF Cable Connections

215IF Module

This section describes how to connect cables inside the control panel of the 215IF Module
mounted in an MP900-Series Machine Controller.

Fig. D.1 215IF Transmission Line Connection Example (JC215-01)

• For connections between Communications Interface Modules, connect the MR-8LM(G)

terminals with the same number using in-panel cables.
Connect pins 8 and 1 of the MR-8LM(G) connector to SRD+ and SRD-, respectively.

• Install the JC215-01 on the input and output sides of the control panel, and connect the

in-panel and panel-to-panel cables to the JC215-01.

• JC215-01 signal terminals: Both input and output are possible between terminals 1 and 2

or between terminals 3 and 4.

• Where the JC215-01 is installed at the end of the transmission line, always install a termi-

nating resistance (75

Ω) between JC215-01 terminals 1 and 2 or between terminals 3 and

4.

• Connect only one end of each in-panel cable or panel-to-panel cable shield to terminal S

of input JC215-01 or output JC215-01, and connect terminal E to terminal Es in the con-

trol panel using a 1.25 mm

2

ground wire.

8 1

CP-316
(CP-215)

MP920

VS-676H5

VS-676H5

CN1 (/CN7)
MR-8LM (G)

215IF Module

CP-916A
Module

3

4

E

1

2

S

SRD+

Core unit

SRD-

SRD+

SRD-

E

4

3

S

2

1

VS-IPEV-SB 1P

×0.3 mm

In-panel twisted-pair cable

ES

ES

1.25mm

2

min.

In-panel shielded ground wire

Input JC215-01

Output JC215-01

8 1

8 1

8 1

Transmission
line with
built-in filter

Connect this cable
shield to the ES
terminal in the
destination control
panel.