Appendix B 218IF Messages

B.1.2 MEMOBUS Binary Mode

B-6

„

Input Relay Status Read

„

Holding Register Read

MFC: 20H

SFC: 02H

Length: 07H

CPU No.

Set the command length.

Command

Always 20H.

The SFC number is 02H when the relay status is read.
Set 4 bits each for the destination CPU number and the source

CPU number.
Set the leading address of the relays to be read.

Set the number of relays to be read.

(L)

(H)

Reference No.

No. of relays (n)

(L)

(H)

(L)

(H)

7

0

MFC: 20H

SFC: 02H

Length: 03H+

CPU No.

(No.of coils/8)

(L)

(H)

(Relays 1 to 8)

Relays(No.of relays)

(L)

(H)

(L)

(H)

Set the command length.

Response

Always 20H.
The same SFC number as that specified in the command is

returned.
Set 4 bits each for the destination CPU number and the source

CPU number.

The status of the relays is returned.

7

0

MFC: 20H

SFC: 03H

Length: 07H

CPU No.

Set the command length.

Command

Always 20H.
The SFC number is 03H when the holding register contents are

read.
Set 4 bits each for the destination CPU number and the source

CPU number.
Set the leading address of the holding registers to be read.

Set the number of holding registers to be read.

(L)

(H)

Reference No.

No. of registers (n)

(L)

(H)

(L)

(H)

7

0

MFC: 20H

SFC: 03H

Length: 03H+

CPU No.

Data 1

Data n

(L)

(H)

(L)

(H)

(L)

(H)

Set the command length.

Response

Always 20H.

The same SFC number as that specified in the command is

returned.
Set 4 bits each for the destination CPU number and the source

CPU number.

The status of the read holding registers is returned.

7

0

No.of registers×2