B.1.2 memobus binary mode, Coil status read – Yaskawa MP920 Communications Module User Manual
Page 254

B.1 Extended MEMOBUS Messages
B-5
B
B.1.2
MEMOBUS Binary Mode
This mode is the binary mode format for MEMOBUS message transmission.
Coil Status Read
* 1. MFC: Major Function Code
* 2. SFC: Subfunction Code
MFC : 20H
SFC : 01H
CPU No.
Length: 07H
Set the command length.
Command
Always 20H.
The SFC number is 01H when coil status is read.
Set 4 bits each for the destination CPU number and the source
CPU number.
Set the leading address of the coils to be read.
Set the number of the coils to be read.
(L)
(H)
Reference No.
No. of coils (n)
(L)
(H)
(L)
(H)
*1
*2
7
0
MFC: 20H
SFC: 01H
CPU No.
Length: 03H+
(No.of coils/8)
(L)
(H)
(Coils 1 to 8)
Coils (No.of coils)
(L)
(H)
(L)
(H)
Set the response length.
Response
Always 20H.
The same SFC number as that specified in the command is
returned.
Set 4 bits each for the destination CPU number and the source
CPU number.
The status of the read coils is returned.
7
0