7 218IF Module

7.8.6 MP900-Series Machine Controller and MELSEC Register Maps

7-44

7.8.6

MP900-Series Machine Controller and MELSEC Register Maps

The following table shows the correspondences between MP900-Series Machine Controllers
and MELSEC devices. Each MELSEC device is allocated to an MP900-Series Machine
Controller M register (holding register, input register, input relays, or coils). The MW regis-
ters correspond to holding and input registers, and the MB registers correspond to input
relays and coils.

Fig. 7.1 Register Correspondences

F

0

Holding registers

F

0

Input registers

F

0

Input relays

F

0

Coils

Data address

MW/MB/IW/IB

0000

0127
0128

0143
0144

0159
0160

0175
0176

0191
0192

0255
0256

0271
0272

0335
0336

0351
0352

0511
0512

1023
1024

1279
1280

2303
2304

10495

(9999)

Input
Device code: X

Output
Device code: Y

Internal relay
Device code: M

Internal relay
Device code: M

Link relay
Device code: B

Annunciator
Device code: F

Timer contact
Device code: TS

Timer coil
Device code: TC

Counter contact
Device code: CS

Counter coil
Device code: CC

Timer current value
Device code: TN

Data register
Device code: D

Special register
Device code: D

Link register
Device code: W

File register
Device code: R

Counter current
value
Device code: CN

Advertising