L1-02: motor overload protection time – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 100

Advertising
background image

Setting 4: PM Derated Torque Motor

Use this setting when operating a PM motor. PM motors for derated torque have a self-cooling design and the overload tolerance

drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload characteristics,

providing overheat protection across the entire speed range.

Overload Tolerance

Cooling Ability

Overload Characteristics

Continuous

60 s

Motor Speed (%)

Torque (%)

150

10

33

100

120
100

80

50

0.0

Motor is designed to produce 100%

torque at base speed. Built with

effective cooling capabilities.

Reaching 100% when operating at

below the base frequency causes a

motor overload fault (oL1). The drive

fault output closes and the motor coasts

to stop.

n

L1-02: Motor Overload Protection Time

Sets the detection time of motor overheat due to overload. This setting rarely requires adjustment, but should correlate with

the motor overload tolerance protection time for performing a hot start.

No.

Name

Setting Range

Default

L1-02

Motor Overload Protection Time

0.1 to 50.0 minutes

1.0 minute

Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start.

Figure 1.58

illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at

the value of E1-06, Motor Base Speed, with L1-02 set to one minute.
During normal operation, motor overload protection operates in the area between a cold start and a hot start.
• Cold start: Motor protection operation time in response to an overload situation that was suddenly reached when starting a

stationary motor.

• Hot start: Motor protection operation time in response to an overload situation that occurred during sustained operation at

rated current.

Operation time (minutes)

Cold start

Hot start

Motor current (%)

E2-01 = 100% motor current

10

7

3

1

0.4

0.1

0

100

150

200

Figure 1.58 Motor Protection Operation Time

n

Motor Protection Using a Positive Temperature Coefficient (PTC) Thermistor

Connect a motor PTC to an analog input of the drive for motor overheat protection.
When the PTC input signal reaches the motor overheat alarm level, an oH3 alarm will be triggered and the drive will continue

operation as selected in L1-03. When the PTC input signal reaches the overheat fault level, an oH4 fault will be triggered, a

fault signal will be output, and the drive will stop the motor using the stopping method determined in L1-04.

Figure 1.59

shows a PTC connection example for analog input A2. When using analog input A2, be sure to set Jumper S1 on

the control board for voltage input when using this function.

1.8 L: Protection Functions

100

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual