T2: parameter, T2: parameter settings during pm motor auto-tuning – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 155

Advertising
background image

n

T1-07: Motor Base Speed

Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor

with an extended speed range or if using the motor in the field weakening area.

No.

Name

Setting Range

Default

T1-07

Motor Base Speed

0 to 14400 r/min

1750 r/min

n

T1-11: Motor Iron Loss

Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron

loss that the drive automatically calculated when the motor capacity was entered to T1-02. Enter the motor iron loss value

listed to T1-11 if the motor test report is available.

No.

Name

Setting Range

Default

T1-11

Motor Iron Loss

0 to 65535 W

14 W

n

T1-12: T1 Tuning Start

Set T1-12 to 0 to start IM Auto-Tuning.

No.

Name

Setting Range

Default

T1-12

T1 Tuning Start

0

u

T2: Parameter Settings during PM Motor Auto-Tuning

The T2-oo parameters are used to set the Auto-Tuning input data for PM motor tuning.

n

T2-01: PM Motor Auto-Tuning Mode Selection

No.

Name

Setting Range

Default

T2-01

PM Motor Auto-Tuning Mode Selection

0

0

Setting 0: PM Motor Parameter Settings

n

T2-03: PM Motor Type

Selects the type of PM motor the drive will operate.

No.

Name

Setting Range

Default

T2-03

PM Motor Type

0, 1

1

Setting 0: IPM motor

Setting 1: SPM motor

n

T2-04: PM Motor Rated Power

Specifies the motor rated power in kilowatts.

No.

Name

Setting Range

Default

T2-04

PM Motor Rated Power

0.00 to 650.00 kW

Determined by o2-04

and C6-01

n

T2-05: PM Motor Rated Voltage

Sets the motor rated voltage.

No.

Name

Setting Range

Default

T2-05

PM Motor Rated Voltage

0.0 to 733.1 V

575.0 V

1.12 T: Motor Tuning

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

155