Figure 1.56 Analog Output Gain and Bias Setting Example 3

n

H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection

Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters

H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.

No.

Name

Setting Range

Default

H4-07

Multi-Function Analog Output Terminal FM

Signal Level Selection

0 to 2

0

H4-08

Multi-Function Analog Output Terminal AM

Signal Level Selection

0 to 2

0

Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA

u

H5: Serial Communication (APOGEE FLN, BACnet, MEMOBUS/Modbus,
and Metasys N2)

Serial communication is possible in the drive using the built-in RS-422/RS-485 port (terminals R+, R-, S+, S-) and

programmable logic controllers (PLCs) or similar devices running the APOGEE FLN, BACnet, MEMOBUS/Modbus, and

Metasys N2 protocols.
The H5-oo parameters set the drive for APOGEE FLN, BACnet, MEMOBUS/Modbus, and Metasys N2 communications.

Refer to the different communication protocol chapters for detailed descriptions of the H5-oo parameters.