L3-03: Stall Prevention Limit during Acceleration

The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets the

lower limit for this reduction as a percentage of the drive rated current.

No.

Name

Setting Range

Default

L3-03

Stall Prevention Limit during Acceleration

0 to 100%

50%

Stall Prevention level during Acceleration

Output frequency

L3-03

E1-06

Base frequency

L3-02

Figure 1.63 Stall Prevention Level and Limit During Acceleration

n

L3-22: Deceleration Time at Stall Prevention during Acceleration

Sets the brief deceleration time used when stalling occurs while accelerating a PM motor. When set to 0, this function is

disabled and the drive decelerates at the selected deceleration time when stalling occurs.
The function is effective only in OLV/ PM control and when parameter L3-01 is set to 1.

No.

Name

Setting Range

Default

L3-22

Deceleration Time at Stall Prevention During Acceleration

0.0 to 6000.0 s

0.0 s

n

L3-04: Stall Prevention Selection during Deceleration

Stall Prevention during deceleration controls the deceleration based on the DC bus voltage and prevents an overvoltage fault

caused by high inertia or rapid deceleration.

No.

Name

Setting Range

Default

L3-04

Stall Prevention Selection During Deceleration

0, 1, 2, 4, 5

<1>

1

<1> Settings 4 and 5 are not available in OLV/PM.

Setting 0: Disabled

The drive decelerates according to the set deceleration time. With high inertia loads or rapid deceleration, an overvoltage fault

may occur. If an overvoltage fault occurs, use dynamic braking options or switch to another L3-04 selection.

Setting 1: General-Purpose Stall Prevention

The drive tries to decelerate within the set deceleration time. The drive pauses deceleration when the DC bus voltage exceeds

the Stall Prevention level and then continues deceleration when the DC bus voltage drops below that level. Stall Prevention

may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall Prevention depends on the input

voltage setting E1-01.

Drive Input Voltage

Stall Prevention Level during Deceleration

600 V Class

1084 Vdc

Note:

This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider using

a dynamic braking option.

Figure 1.64

illustrates the function of Stall Prevention during deceleration.

1.8 L: Protection Functions

106

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual