Setting

Function

Page

15

Frequency Detection 3

88

16

Frequency Detection 4

88

17

Torque Detection 1 (N.C.)

86

1B

During Baseblock (N.C.)

89

1E

Restart Enabled

89

1F

Motor Overload Alarm (oL1)

89

20

Drive Overheat Pre-Alarm (oH)

89

2F

Maintenance Period

89

37

During Frequency Output

89

38

Drive Enabled

90

39

Watt Hour Pulse Output

90

3A

Drive Overheat Alarm (oH2)

90

3D

During Speed Search

90

3E

PID Feedback Low

90

3F

PID Feedback High

90

4A

During KEB Operation

90

4B

During Short Circuit Braking

90

Setting

Function

Page

4C

During Fast Stop

90

4D

oH Pre-Alarm Time Limit

90

50

Waiting for Run

90

51

Sequence Timer 1 Active

90

52

Sequence Timer 2 Active

91

53

Sequence Timer 3 Active

91

54

Sequence Timer 41 Active

91

58

Underload Detection

91

60

Internal Cooling Fan Alarm

91

71

Secondary PI Feedback Low

91

72

Secondary PI Feedback High

91

A4

BP Drive Relay

91

A5

BP Bypass Relay

91

A6

BP BAS Interlock Relay

91

A9

Relay Operator Control

91

B2

BAS Interlock Relay Contact

91

100 to 1B2 Functions 0 to b2 with Inverse Output

91

Setting 0: During Run

Output closes when the drive is outputting a voltage.

Status

Description

Open

Drive is stopped.

Closed

A Run command is input or the drive is in deceleration or DC injection.

ON

ON

OFF

OFF

ON

OFF

Run command

Baseblock

command

Output

frequency

During Run

Figure 1.39 During Run Time Chart

Setting 1: Zero Speed

Terminal closes when the output frequency or motor speed falls below the minimum output frequency set to E1-09 or b2-01.

Status

Description

Open

Output frequency is above the minimum output frequency set to E1-09 or b2-01

Closed

Output frequency is less than the minimum output frequency set to E1-09 or b2-01

OFF

Output frequency

or

motor speed

Zero Speed

ON

E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)

Figure 1.40 Zero-Speed Time Chart