Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 120

Advertising
background image

n

L8-15: oL2 Characteristics Selection at Low Speeds

Selects whether the drive overload capability (oL fault detection level) is reduced at low speeds to prevent premature output

transistor failures.

Note:

Contact Yaskawa for consultation before disabling this function. Disabling this function may shorten the operating life of the power

transistors.

No.

Name

Setting Range

Default

L8-15

oL2 Characteristics Selection at Low Speed

0, 1

1

Setting 0: Protection Disabled at Low Speed

The overload protection level is not reduced. Frequently operating the drive with high output current at low speed can lead to

premature drive faults.

Setting 1: Protection Enabled at Low Speed

The overload protection level (oL2 fault detection level) is automatically reduced at speeds below 6 Hz. At zero speed, the

overload is derated by 50%.

n

L8-18: Software Current Limit Selection

Enables and disables the Software Current Limit (CLA) protection function to prevent main circuit transistor failures caused

by high current.

Note:

Do not change this setting unless absolutely necessary.

No.

Name

Setting Range

Default

L8-18

Software Current Limit Selection

0, 1

0

Setting 0: Software CLA Disabled

The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.

Setting 1: Software CLA Enabled

When the Software CLA current level is reached, the drive reduces the output voltage to reduce the current. Normal operation

continues when the current level drops below the Software CLA level.

n

L8-27: Overcurrent Detection Gain

Adjusts the overcurrent detection level in OLV/PM control mode. A setting of 100% is equal to the motor rated current. When

the drive rated current is considerably higher than the motor rated current, use this parameter to decrease the overcurrent level

and prevent motor demagnetization from high current.
Overcurrent detection uses the lower value between the overcurrent level for the drive and the motor rated current multiplied

by L8-27.

No.

Name

Setting Range

Default

L8-27

Overcurrent Detection Gain

0.0 to 400.0%

300.0%

n

L8-29: Current Unbalance Detection (LF2)

Enables or disables output current unbalance detection in OLV/PM control mode. Current unbalance can heat a PM motor

and demagnetize the magnets. The current unbalance detection function monitors output current and triggers the LF2 fault to

prevent such motor damage.

No.

Name

Setting Range

Default

L8-29

Current Unbalance Detection (LF2)

0, 1

1

Setting 0: Disabled

No current unbalance protection is provided to the motor.

Setting 1: Enabled

The LF2 fault is triggered if an output current unbalance is detected. Drive output shuts off and the motor coasts to stop.

n

L8-32: Main Contactor and Cooling Fan Power Supply Failure Selection

Determines drive operation when a FAn fault occurs.

1.8 L: Protection Functions

120

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual