Speed estimation type speed search (b3-24 = 1) – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 32

Advertising
background image

Run command

Output

frequency

Output current

OFF

ON

b3-02

Decel time set
set to b3-03

Waits for twice
as long as L2-04

Selected
frequency
reference

Minimum Baseblock Time

(L2-03)

Max. output frequency
or the specified
frequency reference

Figure 1.11 Current Detection Speed Search at Start or Speed Search Command by Digital Input

Notes on Using Current Detection Type Speed Search

• Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection Speed

Search.

• Current Detection Speed Search is not available when using OLV Control for PM motors.
• Increase the minimum baseblock time set to L2-03 if an overcurrent or overvoltage fault occurs when performing Speed

Search after power is restored following a momentary power loss.

n

Speed Estimation Type Speed Search (b3-24 = 1)

This method can be used for a single induction motor connected to a drive. Do not use this method if the motor is one or more

frame size smaller than the drive, at motor speeds above 200 Hz, or when using a single drive to operate more than one motor.
Speed Estimation is executed in the two steps described below:

Step 1: Back EMF Voltage Estimation

This method is used by Speed Search after baseblock (e.g., a power loss where the drive CPU continued to run and the Run

command was kept active). Here, the drive estimates the motor speed by analyzing the back EMF voltage and outputs the

estimated frequency and increases the voltage using the time constant set in parameter L2-04. After that, the motor is accelerated

or decelerated to the frequency reference starting from the detected speed. If there is not enough residual voltage in the motor

windings to perform the calculations described above, the drive will automatically proceed to step 2.

AC power

supply

Output

frequency

Output

current

OFF

ON

Starts at the speed
that was detected

Selected
frequency
reference

Min. Baseblock Time

(L2-03)

Several miliseconds

b3 -05 <1>

Figure 1.12 Speed Search after Baseblock

<1> After AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than

the minimum baseblock time set to L2-03, the drive will wait until the time set to b3-05 has passed after power is restored

before starting Speed Search.

Step 2: Current Injection

Current Injection is performed when there is insufficient residual voltage in the motor after extended power losses, when Speed

Search is applied with the Run command (b3-01 = 1), or when an External search command is used.

1.2 b: Application

32