Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual
Page 277

Point
Numb
er
Point
Type
Point Name
Factory
Default
(SI
Units)
Eng. Units
(SI Units)
Slope
(SI
Units)
Intercept
(SI Units)
On Text
Off Text
Parameter
78
LDI
MF IN 4 MON
OFF
–
1
0
ON
OFF
U1-10 (Bit 5)
79
LAI
PID DEVIATE
0
%
0.01
0
–
–
U5-02
80
LAO
PID I LIMIT
100
%
0.1
0
–
–
b5-04
81
LAO
PID UP LIMIT
100
%
0.1
0
–
–
b5-06
82
LAO
PID OFFS ADJ
100
%
0.1
-100
–
–
b5-07
83
LAO
PID PRI DYTM
0
s
0.1
0
–
–
b5-08
84
LAO
PID FB RMDS
0
–
1
0
–
–
b5-12
85
LAO
PID FB RMDL
0
%
1
0
–
–
b5-13
86
LAO
PID FB RMDT
1
s
0.1
0
–
–
b5-14
87
LAI
PID OUT CAP
0
%
0.01
0
–
–
U5-14
88
LAI
PID REF
0
%
0.01
0
–
–
U5-04
89
LAI
COMM ERR CD
0
–
1
0
–
–
U1-19
90
LDO
COMM FLT
ENA
ENABLE
–
1
0
ENABL
E
DISABLE
H5-05
91
LAO
CBL LOSS FRQ
0
Hz
0.01
0
–
–
d1-04
92
LAO
CBL LOSS TMR
2
s
0.1
0
–
–
H5-09
93
LDI
OK.FAULT
OK
–
1
0
FAULT
OK
U1-12 (Bit 7)
94
LDO
RESET FAULT
NO
–
1
0
RESET
NO
–
95
LDI
DRV COMM
ERR
NO FLT
–
1
0
FAULT
NO FLT
–
96
LDO
EXTERNAL FLT
OK
–
1
0
FAULT
OK
–
97
LDI
MF IN 5 MON
OFF
–
1
0
ON
OFF
U1-10 (Bit 6)
99
LAI
ERROR
STATUS
0
–
1
0
–
–
U1-19
<1> Set H1-03 to 70 , Drive Enable2, for pt 35 to work properly.
C.5 APOGEE FLN Point Database
YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual
277
C
APOGEE FLN (P1) Communications