A.18 defaults by drive model – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 243

Advertising
background image

No.

Name

Unit

Default Settings

Model

5A0125

5A0145

5A0192

5A0242

o2-04

Drive Model Selection

Hex.

D5

D6

D7

D9

E2-11

Motor Rated Power

kW (HP)

90

(125)

110

(150)

160

(200)

185

(250)

b3-04

V/f Gain during Speed Search

%

80

80

80

80

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b8-04

Energy Saving Coefficient Value

61.50

58.67

49.90

42.90

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

125

145

192

242

E2-02

Motor Rated Slip

Hz

1.39

1.40

1.35

1.35

E2-03

Motor No-Load Current

A

37.5

43.2

57.6

57.6

E2-05

Motor Line-to-Line Resistance

Ω

0.079

0.060

0.037

0.037

E2-10

Motor Iron Loss for Torque Compensation

W

2150

2150

2850

2850

L2-02

Momentary Power Loss Ride-Thru Time

s

2.0

2.0

2.0

2.0

L2-03

Momentary Power Loss Minimum Baseblock Time

s

2.0

2.0

2.0

2.0

L2-04

Momentary Power Loss Voltage Recovery Time

s

1.7

1.8

2.0

2.0

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.592

0.646

0.673

0.864

L8-02

Overheat Alarm Level

°C

110

110

110

110

L8-35

Installation Method Selection

0

0

0

0

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

30

30

30

30

A.18 Defaults by Drive Model

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

243

A

Parameter List

Advertising