The parameters shown in, Table 1.1, 1 a: initialization – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 20

Advertising
background image

Table 1.1 Parameters Not Changed by Drive Initialization

No.

Parameter Name

A1-00

Language Selection

A1-02

Control Method Selection

E1-03

V/f Pattern Selection

F6-08

Communication Parameter Reset

L8-35

Installation Selection

o2-04

Drive/kVA Selection

n

A1-04, A1-05: Password and Password Setting

Parameter A1-04 enters the password when the drive is locked; parameter A1-05 is a hidden parameter that sets the password.

No.

Parameter Name

Setting Range

Default

A1-04

Password

0000 to 9999

0000

A1-05

Password Setting

How to Use the Password

The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to

unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following

parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01, A1-02,

A1-03, A1-06, and A2-01 through A2-33.
The instructions below demonstrate how to set password “1234”. An explanation follows on how to enter that password to

unlock the parameters.

Table 1.2 Setting the Password for Parameter Lock

Step

Display/Result

1.

Turn on the power to the drive. The initial display appears.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00 A

DRV

Freq Ref (AI)

Rdy

FWD

LSEQ

LREF

2.

Press

or

until the Parameter Setting Mode screen appears.

HELP

- MODE -

PRG

DATA

Programming

FWD

3.

Press

to enter the parameter menu tree.

-PRMSET-

Initialization

Select Language

PRG

A

1-00= 0

FWD

4.

Select the flashing digits by pressing

F1

,

F2

, or

.

-PRMSET-

Select Language

English

PRG

FWD

A1-

00

= 0

*0*

5.

Select A1-04 by pressing

.

-PRMSET-

A1-

04

= 0

(0~9999)

“0”

PRG

Enter Password

FWD

6.

Press

while holding down

OFF

at the same time. A1-05 will appear.

Note:

A1-05 is hidden and will not display by pressing only

.

-PRMSET-

A1-

05

= 0

(0~9999)

“0”

PRG

Select Password

FWD

7.

Press

.

-PRMSET-

A1- 05 = 0000

(0~9999)

“0”

PRG

Select Password

FWD

0

1.1 A: Initialization

20

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Advertising