Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 89

Advertising
background image

L4-04

Frequency
Detection 4

ON

OFF

L4-03

Output Frequency

or Motor Speed

Figure 1.48 Frequency Detection 4 Example with Positive L3-04 Value

Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 110

for more details.

Setting 1B: During Baseblock (N.C.)

The output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not switch

and no main circuit voltage is output.

Status

Description

Open

Baseblock is being executed.

Closed

Drive is not in a baseblock state.

Setting 1E: Restart Enabled

An output set for “Restart enabled” closes when the drive attempts to restart after a fault has occurred.
The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is

cleared and the drive has attempted to restart. If the drive cannot successfully restart within the number of attempts permitted

by L5-01, a fault will be triggered and the terminal set to 1E will open.

Refer to L5: Fault Restart on page 111

for details on

automatic restart.

Setting 1F: Motor Overload Alarm (oL1)

The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level.

Refer to L1-01: Motor Overload Protection Selection on page 99

.

Setting 20: Drive Overheat Pre-Alarm (oH)

The output closes when the drive heatsink temperature reaches the level specified by parameter L8-02.

Refer to L8-01:

Internal Dynamic Braking Resistor Protection Selection (ERF type) on page 116

for details on drive overheat detection.

Setting 2F: Maintenance Period

The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined

by the estimated performance life span of those components. Components performance life is displayed as a percentage on

the HOA keypad screen.

Setting 37: During Frequency Output

The output closes when the drive is outputting a frequency.

Status

Description

Open

Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.

Closed

Drive is outputting frequency.

1.7 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

89

1

Parameter Details