Setting 70: Drive Enable2

A digital input configured as a Drive Enable2 input (H1-oo = 70) prevents the drive from executing a Run command until

the Drive Enable2 input is closed. When the Drive Enable2 input is open and a Run command is closed, the digital operator

will display “dnE”.
The Run command does not need to be cycled after the Drive Enable2 input is closed. The drive will run when both the Run

and Drive Enable2 inputs are closed. If the Drive Enable2 input is opened while the drive is running, the drive will stop using

the method set by parameter b1-03.

Setting 7A, 7B: KEB Ride-Thru 2 (N.C., N.O.)

An input terminal set to 7A or 7B can trigger Single Drive KEB Ride-Thru during deceleration. L2-29 is disregarded if this

is enabled.

Digital Input Function

Drive Operation

Input Open

Input Closed

Setting 7A (N.C.)

Single Drive KEB Ride-Thru 2

Normal operation

Setting 7B (N.O.)

Normal operation

Single Drive KEB Ride-Thru 2

Note:

Simultaneously assigning KEB Ride-Thru 1 and KEB Ride-Thru 2 to the input terminals will trigger an oPE03 error.

Setting 7C, 7D: Short Circuit Braking (N.O., N.C.) (OLV/PM)

Activates Short Circuit Braking in OLV/PM control mode. By linking all three phases of a PM motor, Short Circuit Braking

creates a braking torque to stop a rotating motor or prevent a motor from coasting due to external forces (such as the windmill

effect in fan applications). Parameter b2-18 limits the current during Short Circuit Braking.

DIgital Input Function

Drive Operation

Input Open

Input Closed

Setting 7C (N.O.)

Normal operation

Short Circuit Braking

Setting 7D (N.C.)

Short-Circuit Braking

Normal operation

Setting A4: BP Emergency Override

When this input is closed the drive will switch into override. If the drive is running the drive will stop running and the motor

will be switched to line voltage. If the drive is not running and dampers are present, they will be actuated. Upon completion

of damper actuation the motor will be run on line voltage.

Setting A5: BP Drive/Bypass Select

Note:

An oPE27 (BP Program Error) will occur if one of the digital inputs is set to A5 and parameter o1-13 or o1-14 is set to 2 (Drive/Bypass).

Status

Description

Open

Bypass mode

Closed

Drive mode

Setting A6: BP BAS Interlock

Indicates that the dampers are open.

Setting A7: BP Customer Safeties

Indicates that customer safeties are in place.

Setting A8: PI2 Disable (N.O.)

Disables the secondary PI controller. Output behavior depends on the setting of S3-12

Setting A9: PI2 Disable (N.C.)

Enables the secondary PI controller (when open, output behavior depends on the setting of S3-12).

Setting AA: PI2 Inverse Operation

Changes the sign of the secondary PI controller input (reverse acting PI control).

Setting AB: PI2 Integral Reset

Resets the secondary PI controller integral value.

1.7 H: Terminal Functions