B4: delay timers – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 36

Advertising
background image

No.

Name

Setting Range

Default

b3-19

Number of Speed Search Restarts

0 to 10

3

n

b3-24: Speed Search Method Selection

Sets the Speed Search method.

No.

Parameter Name

Setting Range

Default

b3-24

Speed Search Method Selection

0, 1

0

Setting 0: Current Detection
Setting 1: Speed Estimation

Note:

Refer to Current Detection Speed Search (b3-24 = 0) on page 31

and

Refer to Speed Estimation Type Speed Search (b3-24 = 1) on page

32

for explanations of the Speed Search methods.

n

b3-25: Speed Search Wait Time

Sets the wait time between Speed Search restarts. Increase the wait time if problems occur with overcurrent, overvoltage, or

if the SEr fault occurs.

No.

Name

Setting Range

Default

b3-25

Speed Search Wait Time

0.0 to 300.0 s

0.5 s

n

b3-27: Start Speed Search Select

Selects a condition to activate Speed Search Selection at Start (b3-01) or External Speed Search Command 1 or 2 from the

multi-function input.

No.

Name

Setting Range

Default

b3-27

Start Speed Search Select

0, 1

0

Setting 0: Triggered when a Run Command Is Issued (Normal)
Setting 1: Triggered when an External Baseblock Is Released

n

b3-33: Speed Search Selection when Run Command is Given during Uv

Activates and deactivates Speed Search at start in accordance with whether a Run command was issued during an undervoltage

(Uv) condition. Function is active when a momentary power loss (L2-01 = 1 or 2), Speed Search at start (b3-01 = 1), and

coasting to a stop (b1-03 = 1) are enabled.

No.

Name

Setting Range

Default

b3-33

Speed Search Selection when Run Command is Given during Uv

0, 1

0

Setting 0: Disabled
Setting 1: Enabled

u

b4: Delay Timers

The timer function is independent of drive operation and can delay the switching of a digital output triggered by a digital input

signal and help eliminate chattering switch noise from sensors. An on-delay and off-delay can be set separately.
To enable the timer function, set a multi-function input to “Timer input” (H1-oo = 18) and set a multi-function output to

“Timer output” (H2-oo = 12). Only one timer can be used.

n

b4-01, b4-02: Timer Function On-Delay, Off-Delay Time

b4-01 sets the on-delay time for switching the timer output. b4-02 sets the off-delay time for switching the timer output.

No.

Name

Setting Range

Default

b4-01

Timer Function On-Delay Time

0.0 to 3000.0 s

0.0 s

b4-02

Timer Function Off-Delay Time

0.0 to 3000.0 s

0.0 s

1.2 b: Application

36

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual