B1-02: run command selection for auto mode – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 25

Advertising
background image

Current Input
Input terminals A1 and A2 can accept a current input signal. Refer to

Table 1.6

to set terminals A1 and A2 for current input.

Table 1.6 Analog Input Settings for Frequency Reference Using a Current Signal

Terminal

Signal

Level

Parameter Settings

Notes

Signal Level

Selection

Function

Selection

Gain

Bias

A1

4 to 20 mA

H3-01 = 2

H3-02 = 0

(Frequency

Reference Bias)

H3-03

H3-04

Make sure to set Jumper S1 on the

terminal board to “I” for current

input.

0 to 20 mA

H3-01 = 3

A2

4 to 20 mA

H3-09 = 2

H3-10 = 0

(Frequency Bias)

H3-11

H3-12

0 to 20 mA

H3-09 = 3

Drive

A1 Analog Input 1

0 or 4 to 20 mA

AC Analog input common

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

V

I

A1 A2

Jumper S1
Terminal A1/A2
Voltage/Current
Selection

V

I

A1 A2

Figure 1.2 Setting the Frequency Reference as a Current Signal to Terminal A2

Switching between Main/Auxiliary Frequency References

The frequency reference input can be switched between the analog terminals A1 and A2 using multi-speed inputs.

Refer to

Multi-Step Speed Selection on page 56

for details on using this function.

Setting 2: Serial Communication (APOGEE FLN, BACnet, MEMOBUS/Modbus, Metasys N2)

This setting requires entering the frequency reference via the RS-422/RS-485 serial communications port (control terminals

R+, R-, S+, and S-).

Refer to MEMOBUS/Modbus Configuration on page 302

for instructions.

Setting 3: Option Card

This setting requires entering the frequency reference via an option board plugged into connector CN5 on the drive control

board. Consult the option card manual for instructions on integrating the drive with the communication system.

Note:

If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Programming Error will

be displayed on the HOA keypad and the drive will not run.

n

b1-02: Run Command Selection for AUTO Mode

Determines the Run command selection for AUTO mode.

No.

Parameter Name

Setting Range

Default

b1-02

Run Command Selection for AUTO Mode

1 to 3

1

Setting 1: Control Circuit Terminal

This setting requires entering the Run command via the digital input terminals using one of following sequences:
• 2-Wire sequence 1:

Two inputs (FWD/Stop-REV/Stop). Set A1-03 to 2220 to initialize the drive and preset terminals S1 and S2 to these

functions. This is the default setting of the drive.

Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-

Wire Sequence on page 78

.

• 2-Wire sequence 2:

Two inputs (Start/Stop-FWD/REV).

Refer to Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2 on

page 78

.

• 3-Wire sequence:

1.2 b: Application

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

25

1

Parameter Details