L8-07: Output Phase Loss Protection Selection

Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.

Note:

1. Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable

this parameter in such cases.

2. Output phase loss detection is not possible when the drive is running a PM motor with light load.

No.

Name

Setting Range

Default

L8-07

Output Phase Loss Protection Selection

0 to 2

1

Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost

An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.

Setting 2: Fault when Two Phases Are Lost

An output phase loss fault (LF) is triggered when two or more output phases are lost. The output shuts off and the motor coasts

to stop.

n

L8-09: Output Ground Fault Detection Selection

Enables or disables the output ground fault detection.

No.

Name

Setting Range

Default

L8-09

Output Ground Fault Detection Selection

0, 1

Determined by

o2-04

Setting 0: Disabled

Ground faults are not detected.

Setting 1: Enabled

A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.

n

L8-10: Heatsink Cooling Fan Operation Selection

Selects the heatsink cooling fan operation.

No.

Name

Setting Range

Default

L8-10

Heatsink Cooling Fan Operation Selection

0, 1

0

Setting 0: Run with Timer

The fan is switched on when a Run command is active and switched off with the delay set to parameter L8-11 after releasing

the Run command. This setting extends the fan lifetime.

Setting 1: Run Always

The fan runs when power is supplied to the drive.

n

L8-11: Heatsink Cooling Fan Off-Delay Time

Sets the cooling fan switch off-delay time if parameter L8-10 is set to 0.

No.

Name

Setting Range

Default

L8-11

Heatsink Cooling Fan Off-Delay Time

0 to 300 s

300 s

n

L8-12: Ambient Temperature Setting

Automatically adapts the drive rated current to safe values when used with parameter L8-35. This eliminates the need to reduce

the drive rated current when the temperature where the drive is mounted is above the specified values.

No.

Name

Setting Range

Default

L8-12

Ambient Temperature Setting

-10 to +50 °C

40 °C

1.8 L: Protection Functions

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

119

1