A.18 defaults by drive model – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 242

Advertising
background image

No.

Name

Unit

Default Settings

Model

5A0041

5A0052

5A0062

o2-04

Drive Model Selection

Hex.

CF

D1

D2

E2-11

Motor Rated Power

kW (HP)

30

(40)

37

(50)

45

(60)

b3-04

V/f Gain during Speed Search

%

80

80

80

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

b8-04

Energy Saving Coefficient Value

115.57

97.01

90.07

C6-02

Carrier Frequency Selection

7

7

7

E2-01

Motor Rated Current

A

41

52

62

E2-02

Motor Rated Slip

Hz

1.8

1.33

1.6

E2-03

Motor No-Load Current

A

12.3

15.6

18.8

E2-05

Motor Line-to-Line Resistance

Ω

0.438

0.267

0.21

E2-10

Motor Iron Loss for Torque Compensation

W

750

925

1125

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

1.2

1.2

1.5

L2-04

Momentary Power Loss Voltage Recovery Time

s

1.1

1.2

1.3

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.323

0.32

0.387

L8-02

Overheat Alarm Level

°C

110

110

110

L8-35

Installation Method Selection

2

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

No.

Name

Unit

Default Settings

Model

5A0077

5A0099

o2-04

Drive Model Selection

Hex.

D3

D4

E2-11

Motor Rated Power

kW (HP)

55

(75)

75

(100)

b3-04

V/f Gain during Speed Search

%

80

80

b3-06

Output Current 1 during Speed Search

0.5

0.5

b8-04

Energy Saving Coefficient Value

80.87

70.07

C6-02

Carrier Frequency Selection

7

7

E2-01

Motor Rated Current

A

77

99

E2-02

Motor Rated Slip

Hz

1.46

1.39

E2-03

Motor No-Load Current

A

23.1

29.7

E2-05

Motor Line-to-Line Resistance

Ω

0.15

0.099

E2-10

Motor Iron Loss for Torque Compensation

W

1260

1600

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

1.8

1.8

L2-04

Momentary Power Loss Voltage Recovery Time

s

1.5

1.6

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.317

0.533

L8-02

Overheat Alarm Level

°C

110

110

L8-35

Installation Method Selection

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

n1-03

Hunting Prevention Time Constant

ms

10

30

A.18 Defaults by Drive Model

242

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Advertising