Contents

002CH

Drive Status 2
bit 0

During Run

bit 1

Zero Speed

bit 2

Speed Agree

bit 3

User Speed Agree

bit 4

Frequency Detection 1

bit 5

Frequency Detection 2

bit 6

Drive Ready

bit 7

During Undervoltage

bit 8

During Baseblock

bit 9

Frequency Reference from Operator Keypad

bit A

Run Command from Operator Keypad

bit B

Over/Undertorque 1

bit C

Frequency Reference Loss

bit D

During Fault Restart

bit E

Fault

bit F

Communication Timeout

002DH

Output Terminal Status
bit 0

Multi-Function Contact Output 1 (terminal M1-M2)

bit 1

Multi-Function Contact Output 2 (terminal M3-M4)

bit 2

Multi-Function Contact Output 3 (terminal M5-M6)

bit 3 to 6

Reserved

bit 7

Fault Contact Output (terminal MA/MB-MC)

bit 8 to F

Reserved

002EH

Reserved

002FH

Frequency Reference Bias (from Up/Down 2 Function), 0.1% units

0030H

Reserved

0031H

DC Bus Voltage, 1 Vdc units

0032H, 0033H

Reserved

0034H

Product Code 1 [ASCII], Product Type (Z0 for Z1000)

0035H

Product Code 2 [ASCII], Region Code

0036H, 0037H

Reserved

0038H

PI Feedback, 0.1% units, unsigned, 100% / max. output frequency

0039H

PI Input, 0.1% units, signed, 100% / max. output frequency

003AH

PI Output, 0.1% units, signed, 100% / max. output frequency

003BH, 003CH

Reserved

003DH

Communications Error Contents

<2>

bit 0

CRC Error

bit 1

Data Length Error

bit 2

Reserved

bit 3

Parity Error

bit 4

Overrun Error

bit 5

Framing Error

bit 6

Timeout

bit 7 to F

Reserved

003EH

Output Frequency

r/min

<4>

003FH

0.01% units

0040H to 004AH

Used for various monitors U1-oo.

Refer to U: Monitors on page 232

for parameter details.

E.9 MEMOBUS/Modbus Data Table