L4: speed detection – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 110

Advertising
background image

n

L3-25: Load Inertia Ratio

Determines the ratio between the rotor inertia and the load. Set this parameter when using Single Drive KEB 2 (L2-29 = 1),

Intelligent Stall Prevention during deceleration (L3-04 = 2), or the overvoltage suppression function (L3-11 = 1).

Note:

This function is available in OLV/PM control mode.

No.

Name

Setting Range

Default

L3-25

Load Inertia Ratio

0.0 to 1000.0

1.0

When set incorrectly, a fairly large current ripple can result during Single Drive KEB 2 (L2-29 = 1). This may cause overvoltage

suppression (L3-11 = 1) or other faults such as ov, Uv1, and oC.
Calculate parameter L3-25 in the formula below:

L3-25 =

Machine Inertia

Motor Inertia

n

L3-26: Additional DC Bus Capacitors

Sets the capacity of any additionally installed DC bus capacitors. This data is used in calculations for Single Drive KEB Ride-

Thru 2. Adjust this setting only if external capacity is connected to the DC bus and Single Drive KEB 2 is used.

No.

Name

Setting Range

Default

L3-26

Additional DC Bus Capacitors

0 to 65000 μF

0 μF

n

L3-27: Stall Prevention Detection Time

Sets a delay time from when the Stall Prevention level is reached and the actual Stall Prevention function is activated.

No.

Name

Setting Range

Default

L3-27

Stall Prevention Detection Time

0 to 5000 ms

50 ms

u

L4: Speed Detection

These parameters set up the speed agree and speed detection functions that can be assigned to the multi-function output

terminals.
The speed is detected using the motor speed when A1-02 = 3 or 7.

n

L4-01, L4-02: Speed Agreement Detection Level and Detection Width

Parameter L4-01 sets the detection level for the digital output functions Speed agree 1, User-set speed agree 1, Frequency

detection 1, and Frequency detection 2.
Parameter L4-02 sets the hysteresis level for these functions.

No.

Name

Setting Range

Default

L4-01

Speed Agreement Detection Level

0.0 to 240.0 Hz

0.0 Hz

L4-02

Speed Agreement Detection Width

0.0 to 20.0 Hz

2.0 Hz

Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 82

, Settings 2, 3, 4, and 5.

n

L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-)

Parameter L4-03 sets the detection level for the digital output functions Speed agree 2, User-set speed agree 2, Frequency

detection 3, and Frequency detection 4.
Parameter L4-04 sets the hysteresis level for these functions.

No.

Name

Setting Range

Default

L4-03

Speed Agreement Detection Level (+/-)

-240.0 to 240.0 Hz

0.0 Hz

L4-04

Speed Agreement Detection Width (+/-)

0.0 to 20.0 Hz

2.0 Hz

Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 82

, Settings 13, 14, 15, and

16.

1.8 L: Protection Functions

110

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual