N: special adjustments, N1: hunting prevention, 9 n: special adjustments – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 123

Advertising
background image

1.9 n: Special Adjustments

These parameters control a variety of specialized adjustments and functions, including Hunting Prevention, High Slip Braking,

resistance between motor lines, and PM motor control functions.

u

n1: Hunting Prevention

Hunting Prevention prevents the drive from hunting as a result of low inertia and operating with light load. Hunting often

occurs with a high carrier frequency and an output frequency below 30 Hz.

n

n1-01: Hunting Prevention Selection

Enables or disables the Hunting Prevention function.

Note:

This function is available only when using V/f Control. Disable Hunting Prevention when drive response is more important than suppressing

motor oscillation. This function may be disabled without problems in applications with high inertia loads or relatively heavy loads.

No.

Name

Setting Range

Default

n1-01

Hunting Prevention Selection

0, 1

1

Setting 0: Disabled

Setting 1: Enabled

n

n1-02: Hunting Prevention Gain Setting

Sets the gain for the Hunting Prevention Function.

No.

Name

Setting Range

Default

n1-02

Hunting Prevention Gain Setting

0.00 to 2.50

1.00

Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
• If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases.
• If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.

n

n1-03: Hunting Prevention Time Constant

Determines the responsiveness of the Hunting Prevention function (affects the primary delay time for Hunting Prevention).

No.

Name

Setting Range

Default

n1-03

Hunting Prevention Time Constant

0 to 500 ms

Determined by

o2-04

Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
• Increase this value for applications with a large load inertia. A higher setting leads to slower response, which can result in

oscillation at lower frequencies.

• Lower this setting if oscillation occurs at low speed.

n

n1-05: Hunting Prevention Gain while in Reverse

This parameter functions the same as n1-02, except it is used when rotating in reverse. See the explanation for n1-02.

Note:

n1-02 is enabled for forward and reverse operation when n1-05 = 0.0 ms.

No.

Name

Setting Range

Default

n1-05

Hunting Prevention Gain while in Reverse

0.00 to 2.50

0.00

1.9 n: Special Adjustments

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

123