H4: multi-function analog outputs – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 96

Advertising
background image

Setting 7: Torque Detection Level

Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog input.

The analog input replaces the level set to L6-02. An analog input of 100% (10 V or 20 mA) sets a torque detection level equal

to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection level settings are required.

Refer to L6: Torque Detection on page 114

for details on torque detection.

Setting 8: Stall Prevention Level

Allows an analog input signal to adjust the Stall Prevention level.

Figure 1.54

shows the setting characteristics. The drive will

use the lower value of the Stall Prevention level set to L3-06 or the level coming from the selected analog input terminal.

Stall Prevention Level during Run

30%

100%

Analog Input Level

30%

100%

0

Figure 1.54 Stall Prevention During Run Using an Analog Input Terminal

Setting 9: Output Frequency Lower Limit Level

The user can adjust the lower limit of the output frequency using an analog input signal.

Setting B: PI Feedback

Supplies the PI feedback value. This setting requires PI operation to be enabled in b5-01.

Refer to PI Feedback Input

Methods on page 38

.

Setting C: PI Setpoint

Supplies the PI setpoint value and makes the frequency reference selected in parameter b1-01 no longer the PI setpoint. PI

operation to be enabled in b5-01 to use this setting.

Refer to PI Setpoint Input Methods on page 37

.

Setting D: Frequency Bias

The input value of an analog input set to this function will be added to the frequency reference. This function can be used with

any frequency reference source.

Setting E: Motor Temperature

In addition to motor overload fault detection oL1, it is possible to use a PTC (Positive Temperature Coefficient) thermistor

for motor insulation protection.

Setting F: Through Mode

When set to F, an input does not affect any drive function, but the input level can still be read out by a PLC via APOGEE

FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 communications.

Setting 16: Differential PI Feedback

If an analog value is set for this function, the PI controller is set for differential feedback. The difference of the PI feedback

input value and the differential feedback input value builds the feedback value used to calculate the PI input.

Refer to PI

Feedback Input Methods on page 38

.

u

H4: Multi-Function Analog Outputs

These parameters assign functions to analog output terminals FM and AM for monitoring a specific aspect of drive

performance.

n

H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection

Sets the desired drive monitor parameter Uo-oo to output as an analog value via terminal FM and AM.

Refer to U: Monitor

Parameters on page 158

for a list of all monitors. The “Analog Output Level” column indicates whether a monitor can be

used for analog output.
Example: Enter “103” for U1-03.

1.7 H: Terminal Functions

96

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

Advertising