b5-01: PI Function Setting

Enables or disables the PI operation and selects the PI operation mode.

No.

Parameter Name

Setting Range

Default

b5-01

PI Function Setting

0, 1, 3

0

Setting 0: PI Disabled
Setting 1: Output Frequency = PI Output 1

The PI controller is enabled and the PI output builds the frequency reference.

Setting 3: Output Frequency = Frequency Reference + PI Output 1

The PI controller is enabled and the PI output is added to the frequency reference.

n

b5-02: Proportional Gain Setting (P)

Sets the P gain applied to the PI input. Larger values will tend to reduce the error but may cause oscillations if set too high,

while lower values may allow too much offset between the setpoint and feedback.

No.

Name

Setting Range

Default

b5-02

Proportional Gain Setting (P)

0.00 to 25.00

2.00

n

b5-03: Integral Time Setting (I)

Sets the time constant used to calculate the integral of the PI input. The shorter the integral time set to b5-03, the faster the

offset will be eliminated. If the integral time is set too short, however, overshoot or oscillation may occur. To turn off the

integral time, set b5-03 to 0.00.

No.

Name

Setting Range

Default

b5-03

Integral Time Setting (I)

0.0 to 360.0 s

0.5 s

n

b5-04: Integral Limit Setting

Sets the maximum output possible from the integral block as a percentage of the maximum frequency (E1-04).

No.

Name

Setting Range

Default

b5-04

Integral Limit Setting

0.0 to 100.0%

100.0%

Note:

On some applications, especially those with rapidly varying loads, the output of the PI function may show a fair amount of oscillation.

Program b5-04 to apply a limit to the integral output and suppress this oscillation.

n

b5-06: PI Output Limit

Sets the maximum output possible from the entire PI controller as a percentage of the maximum frequency (E1-04).

No.

Name

Setting Range

Default

b5-06

PI Output Limit

0.0 to 100.0%

100.0%

n

b5-07: PI Offset Adjustment

Sets the offset added to the PI controller output as a percentage of the maximum frequency (E1-04).

No.

Name

Setting Range

Default

b5-07

PI Offset Adjustment

-100.0 to 100.0%

0.0%

n

b5-08: PI Primary Delay Time Constant

Sets the time constant for the filter applied to the output of the PI controller. Normally, change is not required.

No.

Name

Setting Range

Default

b5-08

PI Primary Delay Time Constant

0.00 to 10.00 s

0.00 s

Note:

Useful when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant frequency.

Increasing this time constant may reduce the responsiveness of the drive.

1.2 b: Application

40

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual