5 e: motor parameters, Setting a custom v/f pattern (setting f: default) – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 65

Advertising
background image

Table 1.25 Derated Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

14.4

575

1.3

25

50

100.6

V

oltage (V)

Frequency (Hz)

0

17.3

575

1.3

25

50

143.8

V

oltage (V)

Frequency (Hz)

0

14.4

575

1.5

30

60

100.6

V

oltage (V)

Frequency (Hz)

0

17.3

575

1.5

30

60

143.8

V

oltage (V)

Frequency (Hz)

Table 1.26 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

20.1

575

1.3 2.5

50

43.1

V

oltage (V)

Frequency (Hz)

0

25.9

575

1.3 2.5

50

57.5

V

oltage (V)

Frequency (Hz)

0

20.1

575

1.5 3

60

43.1

V

oltage (V)

Frequency (Hz)

0

31.6

575

1.5 3

60

57.5

V

oltage (V)

Frequency (Hz)

Table 1.27 Constant Output, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

17.3

34.5

575

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

17.3

34.5

575

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

17.3

34.5

575

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

17.3

575

1.5 3

60

34.5

V

oltage (V)

Frequency (Hz)

Setting a Custom V/f Pattern (Setting F: Default)

Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When initialized, the default values for parameters E1-04 to E1-13 will be equal to Predefined V/f pattern 1.

n

V/f Pattern Settings E1-04 to E1-13

If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04

through E1-13. To create a new V/f pattern, set E1-03 to F.

Refer to V/f Pattern on page 66

for an example custom V/f

pattern.

Note:

Certain E1-oo parameters might not be visible depending on the control mode.

Refer to Parameter List on page 183

for details.

No.

Parameter Name

Setting Range

Default

E1-04

Maximum Output Frequency

40.0 to 240.0 Hz

<1>

E1-05

Maximum Voltage

0.0 to 733.1 V

<1>

E1-06

Base Frequency

0.0 to 240.0 Hz

<1>

E1-07

Middle Output Frequency

0.0 to 240.0 Hz

30.0 Hz

E1-08

Middle Output Frequency Voltage

0.0 to 733.1 V

143.8 V

E1-09

Minimum Output Frequency

0.0 to 240.0 Hz

<1>

E1-10

Minimum Output Frequency Voltage

0.0 to 733.1 V

<2>

E1-11

Middle Output Frequency 2

0.0 to 240.0 Hz

0.0 Hz

<3>

E1-12

Middle Output Frequency Voltage 2

0.0 to 733.1 V

0.0 V

<3>

E1-13

Base Voltage

0.0 to 733.1 V

0.0 V

<1> Default setting is dependent on parameter A1-02, Control Mode Selection.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Parameter ignored when E1-11 and E1-12 are set to 0.0.

1.5 E: Motor Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

65