C.3 Connecting to a Network

This section explains how to connect the drive to an APOGEE FLN network and the network termination required for a

connection.

u

Network Cable Connection

Follow the instructions below to connect the drive to an APOGEE FLN network.

1.

With the power shut off, connect the communications cable to the drive and the master. Use terminal TB3 for APOGEE

FLN.

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

(TB3)

S–
S+
R–
R+
IG

Send (–)
Send (+)
Receive (–)
Receive (+)
Shield Ground

IG R+ R- S+ S-

Figure C.1 Serial Communications Cable Connection Terminal (TB3)

Note:

Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for

the communications cables, and properly shielded clamps to prevent problems with noise. When using RS-485

communications, connect S+ to R+, and S- to R- as shown in the diagram below.

2.

Check or set the termination resistor selection at all slaves. Use the description in

Network Termination

on page

249

for slaves that are Z1000 drives.

3.

Switch the power on.

4.

Set the parameters needed for serial communications (H5-01 through H5-12) using the HOA keypad.

5.

Shut the power off and wait until the drive display goes out completely.

6.

Turn the power back on.

7.

The drive is now ready to begin communicating with the master.