Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 95

Advertising
background image

Setting 0: Frequency Bias

The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency

reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also

when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference

by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input

terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.

Setting 1: Frequency Gain

The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog

input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.

Setting 2: Auxiliary Reference 1

Sets the auxiliary frequency reference 1 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 56

for details.

Setting 3: Auxiliary Reference 2

Sets the auxiliary frequency reference 2 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 56

for details.

Setting 4: Output Voltage Bias

Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available

only when using V/f Control.

Setting 5: Accel/Decel Time Gain

Adjusts the gain level for the acceleration and deceleration times set to parameters C1-01 through C1-08.
The drive acceleration time is calculated by multiplying the gain level to C1-oo as follows:
C1-oo × Accel/decel time gain = Drive accel/decel time

100%

50%

0

5 V

10 V

1V 2V

20%
10%

Acceleration/deceleration gain from 1 to 10 V

(10 V)

Input Voltage (V)

× 10 (%)

=

Figure 1.52 Accel/Decel Time Gain with Analog Input Terminal

Setting 6: DC Injection Braking Current

The current level used for DC Injection Braking is set as a percentage of the drive rated current.

Drive Rated

Current

0

(4)

100%

10 V

(20 mA)

DC Injection Braking Current Level

Figure 1.53 DC Injection Braking Current Using an Analog Input Terminal

1.7 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

95

1

Parameter Details

Advertising