A2: user parameters, A1-06: application preset – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 22

Advertising
background image

Step

Display/Result

7.

Press

and scroll to A1-02.

-PRMSET-

PRG

Control Method

FWD

A1-

02

= 0

0

V/f Control

8.

Press

to display the value set to A1-02. If the first “0” blinks, parameter settings are unlocked.

-PRMSET-

PRG

Control Method

FWD

A1-02=

0

V/f Control

0

9.

Use

and

to change the value if desired (though changing the control mode at this point is

not typically done).

-PRMSET-

PRG

Control Method

FWD

A1-02=

0

PM OpenLoop Vect

5

10.

Press

to save the setting, or press

to return to the previous display without saving changes.

Entry Accepted

11.

The display automatically returns to the parameter display.

-PRMSET-

Initialization

Select Language

PRG

A

1-00= 0

FWD

Note:

1. Parameter settings can be edited after entering the correct password.
2. Performing a 2-Wire or 3-Wire initialization resets the password to “0000”.

n

A1-06: Application Preset

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these

Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters

to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.

User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple

menus.

u

A2: User Parameters

n

A2-01 to A2-32: User Parameters 1 to 32

The user can select up to 32 parameters and assign them to parameters A2-01 through A2-32 to provide quicker access by

eliminating the need to scroll through multiple menus. The User Parameter list can also save the most recently edited

parameters.

No.

Parameter Name

Setting Range

Default

A2-01 to A2-32

User Parameters 1 to 32

A1-00 to S6-07

Determined by

A1-06

<1>

<1> A1-06 determines how parameters edited by the user are saved to the list of User Parameters, A2-01 through A2-32.

Saving User Parameters

To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then enter

the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01 to 1 to

restrict access so users can only set and refer to the parameters saved as User Parameters.

1.1 A: Initialization

22

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual