Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 141

Advertising
background image

n

S3-03: Secondary PI Display Digits

Sets the decimal place display for secondary PI units.

No.

Name

Setting Range

Default

S3-03

Secondary PI Display Digits

0 to 3

2

Setting 0: No Decimal Places
Setting 1: One Decimal Place
Setting 2: Two Decimal Places
Setting 3: Three Decimal Places

n

S3-04: Secondary PI Unit Selection

Sets units for secondary PI control function.

No.

Name

Setting Range

Default

S3-04

Secondary PI Unit Selection

0 to 15

15

Setting 0: Inch of Water (WC)
Setting 1: Pounds per Square Inch (PSI)
Setting 2: Gallons per Minute (GPM)
Setting 3: Degrees Fahrenheit (F)
Setting 4: Cubic Feet per Minute (CFM)
Setting 5: Cubic Meters per Hour (CMH)
Setting 6: Liters per Hour (LPH)
Setting 7: Liters per Second (LPS)
Setting 8: Bar (Bar)
Setting 9: Pascals (Pa)
Setting 10: Degrees Celsius (C)
Setting 11: Meters (Mtr) (Ft: Feet)
Setting 12: Liters per Minute (LPM)
Setting 13: Cubic Meters per Minute (CMM)
Setting 14: No Unit
Setting 15: Percentage (%)

n

S3-05: Secondary PI Setpoint Value

Sets the secondary PI controller target value

No.

Name

Setting Range

Default

S3-05

Secondary PI Setpoint Value

0.00 to 600.00

<1>

0.00

<2>

<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.

n

S3-06: Secondary PI Proportional Gain Setting

Sets the proportional gain of the secondary PI controller. A setting of 0.00 disables P control.

No.

Name

Setting Range

Default

S3-06

Secondary PI Proportional Gain Setting

0.00 to 25.00

1.00

n

S3-07: Secondary PI Integral Time Setting

Sets the integral time for the secondary PI controller. A setting of 0.0s disables integral control.

No.

Name

Setting Range

Default

S3-07

Secondary PI Integral Time Setting

0.0 to 360.0 s

1.0 s

1.11 S: Special Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

141

1

Parameter Details