d7: Offset Frequency

n

d7-01 to d7-03: Offset Frequency 1 to 3

Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed

for Offset frequency 1, 2, and 3 (H1-oo = 44, 45, 46). The selected offset values are added together if multiple inputs are

closed simultaneously.

No.

Parameter Name

Setting Range

Default

d7-01

Offset Frequency 1

-100.0 to 100.0%

0%

d7-02

Offset Frequency 2

-100.0 to 100.0%

0%

d7-03

Offset Frequency 3

-100.0 to 100.0%

0%

Figure 1.28

illustrates the Offset frequency function.

Frequency
reference

Offset Frequency 1 [d7-01]

(Signed)

Offset Frequency 2 [d7-02]

(Signed)

Offset Frequency 3 [d7-03]

(Signed)

Multi-function

input (44) = on

Multi-function

input (45) = on

Multi-function

input (46) = on

SFS

Frequency
reference after
soft starter

Figure 1.28 Offset Frequency Operation