b5-20: PI Setpoint Scaling

Determines the units for the PI Setpoint Value (b5-19) and monitors U5-01 and U5-04.

No.

Parameter Name

Setting Range

Default

b5-20

PI Setpoint Scaling

0 to 3

1

Setting 0: Hz

The setpoint and PI monitors are displayed in Hz with a resolution of 0.01 Hz.

Setting 1: %

The setpoint and PI monitors are displayed as a percentage with a resolution of 0.01%.

Setting 2: r/min

The setpoint and PI monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined

Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PI monitors

U5-01 and U5-04.

n

b5-21: PI Sleep Input Source

Selects the Sleep Function characteristic action. When b5-21 is set to 1, the Sleep Function Start Level (b5-15) is compared

to the output of the drive (Speed Command after PI Block). Use this setting for open loop control.
The Sleep Function Start Level (b5-15) can be compared to the drive input or setpoint by setting b5-21 to 0.
When b5-21 is set to 2, a variation of the Sleep Function called “Snooze” is enabled. See parameters b5-22 to b5-27 for details.

No.

Parameter Name

Setting Range

Default

b5-21

PI Sleep Input Source

0 to 2

1

Setting 0: PI Setpoint
Setting 1: SFS Input
Setting 2: Snooze

n

b5-22: PI Snooze Level

Sets the PI Snooze function start level as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-22

PI Snooze Level

0 to 100%

0%

n

b5-23: PI Snooze Delay Time

Sets the PI Snooze function delay time in seconds.

No.

Parameter Name

Setting Range

Default

b5-23

PI Snooze Delay Time

0 to 2600 s

0 s

n

b5-24: PI Snooze Deactivation Level

When the PI feedback drops below this level, normal operation starts again. Sets as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-24

PI Snooze Deactivation Level

0 to 100%

0%

n

b5-25: PI Setpoint Boost Setting

Temporary increase of PI setpoint to create an overshoot of the intended PI setpoint.

No.

Parameter Name

Setting Range

Default

b5-25

PI Setpoint Boost Setting

0 to 100%

0%

1.2 b: Application