Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 84

Advertising
background image

Setting 2: Speed Agree 1 (f

ref

/f

out

Agree 1)

Closes when the actual output frequency or motor speed is within the Speed Agree Width (L4-02) of the current frequency

reference regardless of the direction.

Status

Description

Open

Output frequency or motor speed does not match the frequency reference while the drive is running.

Closed

Output frequency or motor speed is within the range of frequency reference ±L4-02.

Note:

Detection works in forward and reverse.

L4-02

L4-02

Frequency
reference

Speed agree 1

ON

OFF

Output Frequency

or Motor Speed

Figure 1.41 Speed Agree 1 Time Chart

Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 110

for more details.

Setting 3: User-Set Speed Agree 1 (f

ref

/f

set

Agree 1)

Closes when the actual output frequency or motor speed and the frequency reference are within the speed agree width (L4-02)

of the programmed speed agree level (L4-01).

Status

Description

Open

Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.

Closed

Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

L4-01

L4-01

+

L4-02

L4-01 – L4-02

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

–L4-01

–L4-01

+

L4-02

–L4-01 – L4-02

During

Forward

During Reverse

Output frequency

0 Hz

OFF

OFF

OFF

ON

ON

ON

ON

Output frequency

User Set
Speed Agree 1

Figure 1.42 User Set Speed Agree 1 Time Chart

Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 110

for more instructions.

Setting 4: Frequency Detection 1

The output opens when the output frequency or motor speed rises above the detection level set in L4-01 plus the detection

width set in L4-02. The terminal remains open until the output frequency or motor speed fall below the level set in L4-01.

1.7 H: Terminal Functions

84

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual