No.

Parameter Name

Setting Range

Default

E5-07

Motor q-Axis Inductance

0.00 to 600.00 mH

Determined by

o2-04

n

E5-09: Motor Induction Voltage Constant 1 (Ke)

Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an IPM

motor with variable torque.

No.

Parameter Name

Setting Range

Default

E5-09

Motor Induction Voltage Constant 1

0.0 to 2000.0 mV/(rad/s)

Determined by

o2-04

Note:

Set E5-24 to 0 when setting E5-09. However, setting both E5-09 and E5-24 to 0 will trigger an alarm. An alarm will also be triggered if

neither E5-09 nor E5-24 are set to 0.

n

E5-24: Motor Induction Voltage Constant 2 (Ke)

Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using an

SPM Motor.

No.

Parameter Name

Setting Range

Default

E5-24

Motor Induction Voltage Constant 2

0.0 to 6500.0 mV/(r/min)

Determined by

o2-04

Note:

Set E5-24 to 0.0 when setting E5-09. However, setting both E5-09 and E5-24 to 0.0 will trigger an alarm. An alarm will also be triggered

if neither E5-09 nor E5-24 are set to 0.0.

1.5 E: Motor Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual