Setting 52: Sequence Timer 2 Active

Sequence Timer 2 is active.

Setting 53: Sequence Timer 3 Active

Sequence Timer 3 is active.

Setting 54: Sequence Timer 4 Active

Sequence Timer 4 is active.

Setting 58: Underload Detection

Underload is detected when the output current falls below the underload detection level defined by L6-14 and L6-02.

Setting 60: Internal Cooling Fan Alarm

The output closes when the drive internal cooling fan has failed.

Setting 71: Secondary PI Feedback Low

The PI2 feedback level is too low.

Setting 72: Secondary PI Feedback High

The PI2 feedback level is too high.

Setting A4: BP Drive Relay

Line voltage is being supplied to the drive, and the motor is being run via the drive.

Note:

Available in V/f control mode.

Setting A5: BP Bypass Relay

Line voltage is being supplied directly to the motor.

Note:

Available in V/f control mode.

Setting A6: BP BAS Interlock Relay

Actuation signal for options dampers.

Note:

Available in V/f control mode.

Setting A9: Relay Operator Control

F1 (F2) key toggle relay is output.

Setting B2: BAS Interlock Relay Contact

A Run command is active or voltage is output. Actuation signal for damper.

Setting 100 to 1B2: Functions 0 to B2 with Inverse Output

These settings have the same function as settings 0 to B2, but with inverse output. Set as 1oo, where the “1” indicates inverse

output and the last two digits specify the setting number of the function.
Examples:
• Set 108 for inverse output of “8: During Baseblock (N.O.)”.
• Set 14A for inverse output of “4A: During KEB Operation”.

1.7 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

91