For more information on – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 78

Advertising
background image

Setting

Terminal Status

<1>

Detection Conditions

<2>

Stopping Method

N.O.

N.C.

Always

Detected

Detected

during Run

only

Ramp to Stop

(fault)

Coast to Stop

(fault)

Fast Stop

(fault)

Alarm Only

(continue

running)

24

O

-

O

-

-

O

-

-

25

-

O

O

-

-

O

-

-

26

O

-

-

O

-

O

-

-

27

-

O

-

O

-

O

-

-

28

O

-

O

-

-

-

O

-

29

-

O

O

-

-

-

O

-

2A

O

-

-

O

-

-

O

-

2B

-

O

-

O

-

-

O

-

2C

O

-

O

-

-

-

-

O

2D

-

O

O

-

-

-

-

O

2E

O

-

-

O

-

-

-

O

2F

-

O

-

O

-

-

-

O

<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed.
<2> Determine whether detection for each fault should be enabled only during run or always detected.

Setting 30: PI Integral Reset

Configuring one of the digital inputs for PI integral reset (H1-oo = 30) resets the value of the integral component in PI control

to 0 when the terminal is closed.

Refer to PI Block Diagram on page 39

for more details.

Setting 31: PI Integral Hold

Configuring a digital input for Integral Hold (H1-oo = 31) locks the value of the integral component of the PI control as long

as the input is active. The PI controller resumes integral operation from the hold value as soon as the integral hold input is

released.

Refer to PI Block Diagram on page 39

for more information on this function.

Setting 34: PI Soft Starter Cancel

A digital input configured as a PI soft starter cancel input (H1-oo = 34) enables or disables the PI soft starter and cancels

the PI accel/decel time (b5-17).

Refer to PI Block Diagram on page 39

.

Setting 35: PI Input Level Selection

Allows an input terminal to switch the sign of the PI input.

Refer to PI Block Diagram on page 39

for details.

Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence

Configures the drive for a 2-Wire sequence.
When an input terminal set to 40 closes, the drive operates in the forward direction. When an input set for 41 closes, the drive

operates in reverse. Closing both inputs simultaneously will result in an external fault.

Note:

1. This function cannot be used simultaneously with settings 42 and 43.
2. The same functions are assigned to terminals S1 and S2 when the drive is initialized for 2-Wire sequence.

S1

S2

SN

Drive

Forward Run

Reverse Run

Standard Digital
Input Common

Figure 1.37 Example Wiring Diagram for 2-Wire Sequence

Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2

Sets the drive for 2-Wire sequence 2.

1.7 H: Terminal Functions

78

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual