Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 27

Advertising
background image

Motor coasts

DC Injection Braking

with the current set in

b2-02

Run

command

Output

frequency

ON

OFF

Motor speed

Minimum Baseblock

Time (L2-03)

Figure 1.4 DC Injection Braking to Stop

DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is

removed. It can be calculated by:

DC Injection brake time

(b2-04) x 10 x Output frequency

Max. output frequency (E1-04)

=

Output frequency when

Stop command was entered

100%

(Maximum output

frequency)

10%

DC Injection braking time

b2-04×10

b2-04

Figure 1.5 DC Injection Braking Time Depending on Output Frequency

Note:

If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no

longer occurs.

Setting 3: Coast with Timer

When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start

if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t

after t has expired to start the drive.

Drive output shut off

Run wait time t

Run command

Output

frequency

ON

ON

ON

OFF

OFF

Figure 1.6 Coast with Timer

The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.

1.2 b: Application

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

27

1

Parameter Details