L8-05: input phase loss protection selection, L8-06: input phase loss detection level – Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 118

Advertising
background image

10 s

etc.

time

10 s

10 s

10 s

10 s

10 s

10 s

f

ref

× (L8-19)

f

ref

× (L8-19)

2

f

ref

× (L8-19)

4

f

ref

× (L8-19)

3

f

ref

Output frequency

Reset oH

Alarm

Reset oH

Alarm

Digital ouput (4D)

oH

Alarm

oH

Alarm

oH

Alarm

oH

Alarm

oH alarm number

Figure 1.71 Output Frequency Reduction During Overheat Alarm

n

L8-19: Frequency Reduction Rate during Overheat Pre-Alarm

Specifies the output frequency reduction when L8-03 is set to 4 and an oH alarm is present. Set as a factor of the maximum

output frequency.

No.

Name

Setting Range

Default

L8-19

Frequency Reduction Rate During Overheat Pre-Alarm

0.0 to 100.0%

20.0%

n

L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

No.

Name

Setting Range

Default

L8-05

Input Phase Loss Protection Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage

imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
• The drive is decelerating.
• No Run command is active.
• Output current is less than or equal to 30% of the drive rated current.

n

L8-06: Input Phase Loss Detection Level

Sets the Input Phase Loss Detection (PF) Level.
Triggers PF fault when there is an imbalance larger than the value set to L8-06 in the drive input power voltage.
Detection Level = 100% = Voltage Class ×

No.

Name

Setting Range

Default

L8-06

Input Phase Loss Detection Level

0.0 to 25.0%

Determined by

o2-04

1.8 L: Protection Functions

118

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual