Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 86

Advertising
background image

Setting 7: DC Bus Undervoltage

The output closes when the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A fault in

the DC bus circuit will also cause the terminal set for “DC bus undervoltage” to close.

Status

Description

Open

DC bus voltage is above the level set to L2-05.

Closed

DC bus voltage has fallen below the trip level set to L2-05.

Setting 8: During Baseblock (N.O.)

The output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no

main circuit voltage is output.

Status

Description

Open

Drive is not in a baseblock state.

Closed

Baseblock is being executed.

Setting 9: Frequency Reference Source

Displays the currently selected frequency reference source.

Status

Description

Open

Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15).

Closed

Frequency reference is being sourced from the HOA keypad.

Setting A: Run Command Source

Displays the currently selected Run command source.

Status

Description

Open

Run command is provided from External reference 1 (b1-02) or 2 (b1-16).

Closed

Run command is being sourced from the HOA keypad.

Setting B and 17: Torque Detection 1 (N.O., N.C.)

These digital output functions signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below.

Refer to L6: Torque Detection on page

114

for details.

Setting

Status

Description

B

Closed

Torque detection 1 (N.O.):

Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in

parameter L6-02 for longer than the time specified in parameter L6-03.

17

Open

Torque detection 1 (N.C.):

Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in

parameter L6-02 for longer than the time specified in parameter L6-03.

Setting C: Frequency Reference Loss

An output set for this function closes when frequency reference loss is detected.

Refer to L4-05: Frequency Reference Loss

Detection Selection on page 111

for details.

Setting E: Fault

The output closes when the drive faults (excluding CPF00 and CPF01 faults).

Setting F: Through Mode

Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function in

the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or MEMOBUS/

Modbus communications.

Setting 10: Minor Fault

The output closes when a minor fault condition is present.

1.7 H: Terminal Functions

86

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual