Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 145

Advertising
background image

Fwd Run

Drive Enable-Customer

Safeties

Override (Smoke Purge)

Drive/Bypass Select

BP Drive Relay Contact

Output

BAS Interlock

BP Bypass Relay Contact

Output

BP BAS Interlock Contact

Output

Output Frequency

L2-03

Speed

Search

Occurs

Bypass Run

Figure 1.77 Transfer to Bypass and Safety Circuit

Emergency Override

When the Emergency Override (Smoke Purge) digital input is closed, the drive will perform the transfer.

Refer to Immediate

Transfer to Bypass on page 144

for details.

If programmed, the BP BAS Interlock Relay Contact will close before the transfer occurs. During the transfer process, and if

BAS Interlocks are present, the BAS Interlock Input MFDI must be closed before the drive will close the bypass contactor to

run the motor on line voltage.
When the Emergency Override MFDI is closed, the state of BP Drive/Bypass Select MFDI, Run command, Bypass Run

command and BP Customer Safeties MFDI have no impact on the operation of the system. When Emergency Override opens,

the drive operates based on the other digital input commands. If the drive is commanded to run, the drive will perform the

switch.

Refer to Transfer to Drive Operation on page 144

for details.

1.11 S: Special Parameters

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual

145

1

Parameter Details