Setting 11: Fault Reset Command Active

The output closes when there is an attempt to reset a fault situation from the control circuit terminals, via serial communications,

or using a communications option card.

Setting 12: Timer Output

This setting configures a digital output terminal as the output for the timer function.

Refer to b4: Delay Timers on page 36

for details.

Setting 13: Speed Agree 2 (f

ref

/f

out

Agree 2)

The output closes when the actual output frequency or motor speed is within the speed agree width (L4-04) of the current

frequency reference, regardless of the direction.

Status

Description

Open

Output frequency or motor speed does not match the frequency reference while the drive is running.

Closed

Output frequency or motor speed is within the range of frequency reference ±L4-04.

Note:

Detection works in forward and reverse.

L4-04

L4-04

Frequency
reference

Speed Agree 2

ON

OFF

Output Frequency

or Motor Speed

Figure 1.45 Speed Agree 2 Time Chart

Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 110

for more details.

Setting 14: User-Set Speed Agree 2 (f

ref

/f

set

Agree 2)

The output closes when the actual output frequency or motor speed and the frequency reference are within the speed agree

width (L4-04) of the programmed speed agree level (L4-03).

Status

Description

Open

Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04.

Closed

Output frequency or motor speed and the frequency reference are both within the range of L4-03 ±L4-04.

Note:

The detection level L4-03 is a signed value; detection works in the specified direction only.

1.7 H: Terminal Functions

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual