Yaskawa AC Drive Z1000 AC Drive HVAC Fan User Manual

Page 318

Advertising
background image

Register No.

Contents

0022H

Data Link Status
bit 0

Writing data or switching motors

bit 1

Reserved

bit 2
bit 3

Upper or lower limit error

bit 4

Data conformity error

bit 5

Writing to EEPROM

bit 6 to F

Reserved

0023H

Frequency Reference

<1>

0024H

Output Frequency

<1>

0025H

Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)

0026H

Output Current, 0.1 A units

0027H

Output Power

0028H

Reserved

0029H

Fault Contents 2
bit 0

Reserved

bit 1

Ground Fault (GF)

bit 2

Input Phase Loss (PF)

bit 3

Output Phase Loss (LF)

bit 4, bit 5

Reserved

bit 6

Motor Overheat 2 (PTC input) (oH4)

bit 7 to F

Reserved

002AH

Alarm Contents 1
bit 0, 1

Reserved

bit 2

Run Command Input Error (EF)

bit 3

Drive Baseblock (bb)

bit 4

Overtorque Detection 1 (oL3)

bit 5

Heatsink Overheat (oH)

bit 6

Overvoltage (ov)

bit 7

Undervoltage (Uv)

bit 8

Cooling Fan Error (FAn)

bit 9

MEMOBUS/Modbus Communication Error (CE)

bit A

Option Communication Error (bUS)

bit B

Undertorque Detection 1 (UL3)

bit C

Motor Overheat (oH3)

bit D

PI Feedback Loss (FbL, FbH)

bit E

Reserved

bit F

Serial Communication Transmission Error (CALL)

002BH

Input Terminal Status
bit 0

Terminal S1 Closed

bit 1

Terminal S2 Closed

bit 2

Terminal S3 Closed

bit 3

Terminal S4 Closed

bit 4

Terminal S5 Closed

bit 5

Terminal S6 Closed

bit 6

Terminal S7 Closed

bit 7 to F

Reserved

E.9 MEMOBUS/Modbus Data Table

318

YASKAWA ELECTRIC SIEP YAIZ1U 03A YASKAWA AC Drive – Z1000 Programming Manual