Training Manual

Creating a Tuning List

Figure 7 .9.

Tune List Format
Data for PIDtype
format



The Name(s) should match the format names that were assigned in the Input tab. The
Format Type must match the data type of the input (e.g. gain is floating point with x
decimal places, PID type is State). This information may be found in the Help menus
associated with this dialog box). Entry method designates whether an operator entry is
allowed, and if so, whether the data is accepted immediately or a confirmation is
required. High and low limits may be entered if appropriate, along with Engineering
units
. To restrict the conditions under which a parameter may be changed, enter an
expression in the Allow edit when this expression is true field. Display and Entry state
tables
control text associated with the possible entries for the tuning parameter. This
text is contained in the State Table Block. For additional information on state tables,
refer to IB-1800R-SCR, Display Guide.

• The TL block should look like the next figure after you added the required formats.
• You can also change the name of the TL block to TuneList on the General tab of

this block’s Properties.