Sequence Display Lab

C – ADD THE SEQUENCE DISPLAY TO THE DIF BLOCK

1. Double-click on the DIF block

2. Add the display name BATCH to the Display Tag List

3. Under ‘Display to use at power-up’ type BATCH instead of

PID-100

4. Close the block.

D – COMPILE AND DOWNLOAD TO THE CONTROLLER

1. Save your database

2. Compile the database and fix any reported errors. When your

database compiles properly, in the Interface File dialog window
check the first box under “Produce MIF”

The File Name for the MIF file should be
SEQUENCE, which you created in a
previous lab

3. Open the OPC server by clicking on the OPC Server icon on the

top toolbar

4. Make sure the correct Server Name, Server Node and Server are

selected

See the Extended Modbus OPC Server lab
for assistance

5. If you already have a Device configured, double-click to open

the Configuration menu. Make sure the Primary Port settings are
correct.

If you do not already have a device
configured see Chapter 4, Extended
Modbus OPC Server, for assistance

17 - 11