Sequence Lab

• Click on OK to close the dialog box. The Steps tab of the SEQ Properties dialog shows

the step you added.

Figure 12 .21.

SEQ Properties -
Steps Tab

)

Notice that there are columns for the step number, step name, and expression, and

for each output you added in the Outputs tab. Up to 64 outputs can be configured in
one Sequence block, and each output can assume a different state or value for each
step.

• Add more steps as per the following table:

Step # Step Name ChargeV

DrainV Setpoint CtrlMode SetMode

2 Charge True False 0

0 False

3 Heat False

False

90 1 True

4 Cook False

False 90 1 False

5 Cool False

False 20 1 False

6 Drain False

True 0 0 True



The outputs “CtrlMode” and “SetMode” will be used to change the temperature

controller from Manual to Automatic in the Supervisory Message lab.

12 - 15