Process Alarm Display Lab

B - CONFIGURE A HIGH PROCESS ALARM

Step Procedure

Comments

4.

Double-click on the PAD block to open it

Refer to the next figure.

5.

Enter the tag name PALM_H in the Name field.

6.

Using the pull-down menu, change the Trip
Condition to Greater Or Equal

The alarm will activate (trip) when the
process value is greater than or equal to
the trippoint

7.

Enter a trip value of 150

Since the flow is 0 to 200 GPM, the alarm
will trip at 150 GMP or 75%

8.

Select the Display tab of the PAD block

Refer to the next figure.

9.

Change the Display Format field from “Float 6” to
“Float 1” by selecting it with the mouse

The numerical display of the alarm will be
floating point with one place to the right
of the decimal point

10.

In the Engineering Units field, type GPM

11.

Select “Normal” for the Bar Format field

The range fields are activated

12.

Leave the Lo Range at the default value of 0

13.

Change the Hi Range value to 200

14 - 2