Training Manual

CJC and Display Lab

D - CONFIGURE THE BLOCK INPUTS

Step Procedure

Comments

5.

Click on the Inputs tab at the top of the dialog
box

The Inputs window appears

6.

At the bottom of the screen, select the Add
button

The input editing menu appears

7.

Change the name of Input 1 to TI

This will be the temperature value.

8.

In the Line Format field, type TempL

We have not yet set up the display formats; we will
do this in the next part of the lab.

9.

Close the menu

The new input appears on the Inputs window

10.

Click on the Add button again

11.

Give Input 2 the name CJC and type in CJCL
for the format name

This will be the value being used for compensation.

12.

Close the menu

13.

Add Input 3 and give it the name SCRLCNT

This counts the number of times the Scroll Key is
pressed

14.

Use the pulldown menu to change the data type
to Count

15.

Close the menu

You should now have three inputs (TI, CJ and
SCRLCNT) listed in the Inputs window.



C- EDIT THE DISPLAY FORMATS

Step Procedure

Comment

1.

Click on the Formats tab at the top of the dialog
box

The display formats window appears

2.

At the bottom of the screen, select the Add
button

The Format editing menu appears

3.

Select the field showing FMT1 and type in
TempL

This was the format name we used when
configuring the display block inputs

4.

Use the pull-down menu to change the format to
Float2

This will display the input as a floating point
variable with two places to the right of the decimal
point

5.

Change the Low and High limits to -200 and
1200 respectively

This is the range for a Type K thermocouple

6.

Change the Entry Method to None

This is for display only, no operator entry

7.

In the Engineering Units field, type oC

Use a lower-case o, not a zero

16 - 3