Training Manual

Sequence Display Lab

C – ADD AND CONFIGURE THE SEQUENCE DISPLAY BLOCK

Step Procedure

Comments

1. Right-click on the BATCH compound and open it

2. Select DISP from the Algorithms window and place it to the

right of the Sequence Block, below the Digital Output blocks.
Resize the block so it is a large rectangle.

It is helpful to make the Display Block
rather large in this case, to allow space for
the inputs to be correctly and clearly
displayed.

3. Double-click on the Display Block.

Define the general parameters:

4. In the Name field type SeqDisp

5. For the Display Tag, enter BATCH

6. Enter the following for Initial Display Data:

Line 1: Step

We will define an input called Step, which
will be displayed on this line.

Line 2: StepTime

We will define an input that will be
connected to the sequence block’s TIME
attribute, and display it on Line 2

Line 5: “RUN” (must enclose in quotes)

On initial download the word RUN will be
displayed on Line 5.

Line 6: StartPB

We will define an input called StartPB and
its status will be displayed here.

Define the block inputs:

7. Click the Inputs tab

8. Click on the Add button

The Specify Input Data dialog box opens

9. Make the following entries: