Training Manual

Piecewise Linearization Lab

B - CONFIGURE THE INPUTS AND PID BLOCK

Step Procedure

Comments

4. Open the AIN, VCI and PID blocks and make the following

configuration entries:

We will leave all engineering units at 0 to
100 percent for the purposes of this lab.

AIN1

Name: FT-100
Input type: Current

AIN2

Name: LT-100
Input type: Current
Input number: 2

VCI1

Name: STM FLOW
Linearization type: Modified Square Root

VCI2

Name: LEVEL

PID

Name: LIC-100
Feedforward Compensation Type: Add

5. Make the block connections as follows:

FT-100.MODOUT to STM FLOW.MODIN
LT-100.MODOUT to LEVEL.MODIN
LEVEL.R to LIC-100.PVI
STM FLOW.R to LIC-100.FFCI

The strategy should now look something like this:

18 - 3